The North American Electric Reliability Corporation on Nov. 16 submitted for Federal Energy Regulatory Commission approval proposed new Reliability Standards to address reliability risks associated with the integration of computational loads on the Bulk Power System.

Specifically, NERC is seeking Commission approval of proposed new Reliability Standards CLO-001-1, CLO-002-1, and CLO-003-1.

The proposed Reliability Standards respond to the Commission’s July 16, 2026 order in Docket No. RD26-7-000 directing NERC to file one or more Reliability Standards and associated updates to NERC’s Glossary of Terms to address Bulk Power System risks associated with computational loads by December 31, 2026.

“This petition follows NERC’s filing on October 21, 2026 in Docket No. RR27-1-000 in response to the Computational Load Order requesting Commission approval of revisions to the NERC Rules of Procedure to develop registry criteria necessary for the registration of Computational Load Owners and Computational Load Operators so that these entities will be required to comply with the Reliability Standards proposed in this petition,” NERC noted.

The proposed Reliability Standards would help ensure that computational loads are reliably integrated into the Bulk Power System, it said.

NERC is asking that FERC act on the filing in an expedited manner to enable prompt action to address identified risks to the Bulk Power System and grant the regulatory certainty to support integration of computational loads into NERC’s regulatory framework. 

Expedited action is also warranted due to the broad stakeholder support for the proposed Reliability Standards during the development process, it said.

The proposed Reliability Standards, which would be included in a new family of Reliability Standards referred to as “Computational Load Ownership & Operations,” focus on establishing foundational elements needed to reliably integrate large computational loads into the Bulk Power System.

The proposed Reliability Standards leverage insights from NERC’s Level 3 Alert for computational load and materials from a Large Load Working Group to lay the foundation for the integration of computational loads into grid planning (Proposed Reliability Standard CLO-001-1), grid operations (Proposed Reliability Standard CLO002-1), and protection coordination and disturbance monitoring (Proposed Reliability Standard CLO-003-1), as follows:

  • Reliability Standard CLO-001-1 – Computational Load Interconnection, Studies, and Modeling would (i) require Transmission Owners, Distribution Providers, and Generation Owners to establish interconnection requirements for Computational Load Sites (Requirements R1 through R3); (ii) require Transmission Planners and Planning Coordinators to study the impact of interconnecting new or changed Computational Load Sites (Requirement R4); (iii) require Computational Load Owners and other functional entities to coordinate and cooperate with other functional entities performing studies on the interconnection of Computational Load Sites by, for example, providing any necessary data (Requirements R5 through R7); and (iv) establish modeling data requirements, and verification and reporting procedures for the development of planning horizon cases necessary to support analysis of the reliability of the interconnected transmission system (Requirements R8 through R11).
  • Reliability Standard CLO-002-1 – Computational Load Operational Data and Communications is designed to (i) ensure that Transmission Operators, Balancing Authorities, and Reliability Coordinators have the Computational Load Site data and information needed to plan, monitor, and assess the reliable operation of the Bulk Power System (Requirements R1 through R7); and (ii) require Computational Load Operators to respond to Operating Instructions (Requirements R8 and R9); and (iii) establish Interpersonal Communication capabilities at Computational Load Sites with predefined communications protocols to ensure prompt action to prevent or mitigate occurrences that adversely impact the reliability of the Bulk Power System (Requirements R10 through R15).
  • Reliability Standard CLO-003-1 – Computational Load Protection Coordination and Disturbance Monitoring would help (i) ensure that functional entities have high-resolution monitoring data available from Computational Load Sites to facilitate analysis of System Disturbances (Requirements R1 through R8); and (ii) maintain the coordination of Protection Systems at Computational Load Sites (Requirements R9 and R10).

The proposed Reliability Standards introduce new NERC Glossary definitions – “Computational Load Site,” “Computational Load Owner,” and “Computational Load Operator” – to align with the revisions to the NERC Rules of Procedure proposed in the Registry Criteria Petition. 

In addition, NERC proposes to update the definition of Operating Instruction so that it includes instructions pertaining to Computational Load Sites.

NERC is also proposing 4 modifications in proposed Reliability Standards FAC-001-5 and FAC-002-5 to avoid duplicative requirements by excluding Computational Load Sites from the requirements in those standards.

Kyle Turpin, Manager for Energy Policy and Reliability Standards at the American Public Power Association, is a member of NERC’s standard drafting team that was tasked with the creation of computational large load reliability standards.
 

Topics